-
Terminal wiring for electrical energy meters
In meter- or test bench descriptions you can find various expressions, all with the same meaning. -
How long does a no-load test take?
When the voltage is applied with no current flowing in the current circuit, the test output of the meter shall not produce more than one pulse. -
The different current subscripts
Together with tender documents and meter specifications you will find various subscripts related to current. current I without subscriptThis is the actual current flowing trough the energy meter. starting current... -
When do I need Isolation Current Transformers?
Isolation Current Transformers (ICT) are needed to test more than one direct connected energy meter on a test bench with multiple positions, assuming that the I-P links can not be... -
The Standard Transfer Specification STS
The Standard Transfer Specification (STS) has become recognised as the only globally accepted open standard for prepayment systems, ensuring inter-operability between system components from different manufacturers of prepayment systems. -
The four-quadrant diagram in electricity metering
The interactive diagram shows the relationship between the phase angle φ, apparent-, active- and reactive power respective energy in accordance with clauses 12 and 14 of IEC 60375. -
Why do I need a Vector Diagram?
Modern reference standards and calibration devices have usually a graphical function to show the relationship between the voltages and the currents. -
What are harmonics ?
Generally a harmonic is a integer multiple of the fundamental frequency (nominal fn). When we have a fn of 50 Hz, the 3rd harmonics is traveling with 150 Hz. We... -
Calculating Apparent Power
There are two commonly used methods to calculate the apparent power (VA). The traditional method is the vectorial calculation.
Vectorial vs Arithmetic Method -
What is Maximum Demand Measurement?
Demand is a measure of average power consumption over a fixed time interval. Maximum (or peak) demand is the highest demand recorded over the billing period. -
Technical vs Non-Technical Losses
Technical losses are coming from current flowing in electrical installations. They can not be avoided, but reduced by proper installation. Technical losses can be calculated.
What You Need to Know -
Portable Calibrator RS350
The portable reference standard and calibrator RS350 is especially designed for the needs of metering engineers for on-site testing with high precision.

