Class 0.02 Three Phase Multifunctional Standard CL3112D

The CL3112D is a high-precision, multifunctional, cost-effective three-phase standard energy meter developed in compliance with the Recommendation R46 issued by the International Organization of Legal Metrology (OIML). It is designed for the testing and calibration of energy meters, power terminals, and other electrical measuring instruments. It can also be used for the traceability of Class 0.05 and lower-grade energy meter verification devices as well as other metrological equipment.

Reference Standard Meter CL3112D, front view
Reference Standard Meter CL3112D, front view
Reference Standard Meter CL3112D, rear view
Reference Standard Meter CL3112D, rear view

Function

  • It can measure the distortion factor of voltage and current for each phase, as well as analyze the 2nd to 64th harmonics.
  • It is capable of measuring all waveforms specified in Recommendation R46, including peak-top waves, flat-top waves, odd harmonics, subharmonics, high-order harmonics, and zero-crossing waves.

Technical Parameters

Voltage Measurement
Voltage Range30 V … 720 V
Voltage Accuracy± 0.02% (30 V ≤ U ≤ U max)
Current Measurement
Current Range0.3 mA … 120 A
Current Accuracy± 0.02% (10 mA ≤ I ≤ 120 A), ± 0.05% (1 mA ≤ I ≤ 10 mA), ± 0.2% (0.3 mA ≤ I ≤ 1 mA)
Phase Measurement
Phase Range0.00° … 359.99°
Phase Accuracy± 0.01 (I ≥ 10 mA, U ≥ 30 V)
Frequency Measurement
Frequency Range40 Hz … 70 Hz
Frequency Accuracy± 0.01 Hz
Power Factor Measurement
Power Factor Range– 1.0 … 0 … + 1.0
Power Factor Accuracy± 0.0005
Power Measurement
Active / Reactive / Apparent Power Accuracy± 0.02% (30 V ≤ U ≤ U max, 10 mA ≤ I ≤ I max, PF ≥ 0.5)
Electrical Energy Measurement
Active / Reactive Energy Meter Accuracy± 0.02% (30 V ≤ U ≤ U max, 10 mA ≤ I ≤ I max, PF ≥ 0.5)
Pulse Inupt / Pulse Output0 … 50 KHz
Harmonic Power / EnergyHarmonic order 2nd – 20th: ± 0.2% of reading + 0.1% of range;
Harmonic order 21st – 64th: ± 0.6% of reading + 0.15% of range
Other Indicators
Operating Power SourceAC 220 V ± 10%, 50 Hz ± 5%
Power Consumption / Warm-up Time< 120 VA / < 30 mins
Dimensions (mm)(W × H × D): 485 × 133 × 500
WeightApprox. 19 kg
Meter Constant Table
CL3112D power constants
  60 V 120 V 240 V 480 V 600 V
0.01 A 1.8 x 109 1.8 x 109 1.8 x 109 1.8 x 109 1.8 x 109
0.02 A 1.8 x 109 1.8 x 109 1.8 x 109 1.8 x 109 1.8 x 109
0.05 A 1.8 x 109 1.8 x 109 1.8 x 109 1.8 x 109 1.8 x 109
0.1 A 1.8 x 109 1.8 x 109 1.8 x 109 1.25 x 109 1.0 x 109
0.2 A 1.8 x 109 1.8 x 109 1.25x 109 6.25 x 108 5.0 x 109
0.5 A 1.8 x 109 1.0 x 109 5.0 x 108 2.5 x 108 2.0 x 108
1 A 1.0 x 109 5.0 x 108 2.5 x 108 1.25 x 108 1.0 x 108
2 A 5.0 x 108 2.5 x 108 1.25 x 108 6.25 x 107 5.0 x 107
5 A 2.0 x 108 1.0 x 108 5.0 x 107 2.5 x 107 2.0 x 107
10 A 1.0 x 108 5.0 x 107 2.5 x 107 1.25 x 107 1.0 x 107
20 A 5.0 x 107 2.5 x 107 1.25 x 107 6.25 x 106 5.0 x 106
50 A 2.0 x 107 1.0 x 107 5.0 x 106 2.5 x 106 2.0 x 106
100 A 1.0 x 107 5.0 x 106 2.5 x 106 1.25 x 106 1.0 x 106
The table refers to the automatic settings. It's valid for 3 wire- and 4 wire measuring mode.

The output frequency for end of range in voltage/current pair with three phase connection is 50 kHz. The power pulses are on TTL/CMOS level. The burden capacity is > 20 mA.

Calculation formulas

Frequency

frequency calculation
f = frequency
UR = voltage range
IR = current range
c = reference meter constant

Constant

constant calculation

The meter constants can be set in the settings menu or selected automatic. Setting range is 1 i/kWh to 2 x 109 i/kWh.