The Energy Meter Register Resolution

Last Updated

Reading Time: 3 min

The main purpose of an electronic energy meter is the accurate metering of the customer consumption. The meter has registers for storing the various consumption values (kWh, kvar, demand…).
Some customer request to get direct connected energy meters without decimals because they are worried about an eventual overflow.

Transformer operated meters are switching to the next higher dimension (MW, GW).

When does an overflow happen?

energy-meter-display-overflow
energy-meter-display-overflow

We consider a direct connected three-phase meter with 230 V and 100 A. If the customer is permanently consuming the maximum active power, the meter will reach the value in the picture after 167 years. For a single phase meter it’s more than 500 years.

Electronic energy meters have a lifetime of 15 … 20 years, so we will never ever get an overflow with an 8 digit energy register display without decimals.

energy-meter-display-two-decimals-overflow
energy-meter-display-two-decimals-overflow

If we have two decimal digits, the same meter under permanent full load condition reaches the overflow much earlier (single phase 5 years, three-phase 1.6 years).
Once the overflow is reached, we are omitting one decimal digit. So finally we will end up with no decimals and the values given in the first picture.

Decimals in the register display

Its common praxis that energy meters have an 8 digit display with two decimals. There are two main reasons behind, both are related to the meter testing. In the previous blog you have seen the acceptance criteria for the short interruption and voltage dips. There is a formula for the critical change value. To conduct this tests its necessary that the meter has a sufficient display resolution. A meter without decimals will never change the value, but is it Pass?
Definitely not, you simply don’t know the value change (if any).
When look on a graphic for common energy meters with Un= 230 V we can see that a resolution of two decimals is sufficient for taking the values from display reading.
If the meter has an optical port it’s recommended to use this interface to read more accurate. The internal register for CLOU meters is holding 4 decimals.

maximum-allowed-register-value-change
maximum-allowed-register-value-change

The other reason for decimals is the meter constant- and register test.

While the IEC62052-11 requires a meter constant test, the IEC 62058-31 for meter acceptance tests refers to the classical register test.

Meter Constant Test IEC62052-11

This test is for checking the relationship between the test output and the energy meter register. The difference of the value between test output and register content shall not exceed ±1/10th of the meter accuracy class. For full wording look into the standard.

Practically we are counting the pulses and compare with the register reading.
Example:
We have a meter class 1. So the allowed meter constant error is 0.1%.
How much energy do we need to inject to get a doubt-free test result?
To get a resolution of 0.1% we need to count minimum 1000 pulses. Then we divide our 1000 pulses with the meter constant to get the energy value which we have to inject.
A meter with a constant of 400 i/kWh needs 2.5 kWh while a meter with a constant of 2000 kWh needs only 500 Wh. This test is a meter type test. The test institutes will read by optical head, so the required resolution is there. If you want to do this test with your utility laboratory test bench, you either read also the internal register or you multiply the calculated energy value by 10 to gain the required reading accuracy for a meter with two decimals.

Register Test IEC62058-31

The standard for meter acceptance tests is used for routine testing and acceptance tests in utility laboratories. With the register test we are comparing the injected energy with the register incrementation. The injected energy is recorded by the reference standard of the test bench, the register reading can be done manually or with optical head.

How much energy do we need to inject?
The standard wording: This test shall be performed by measuring a sufficient amount of energy to verify that the accuracy of the incrementing register reading is better than ± 1.0%.

To get the required reading accuracy the energy is related to the number of decimals which we can read from the meter.

A meter with two decimals for energy reading needs 1.1 kWh to have a reading better than ± 1.0%. If the meter has three decimals, only 0.11 kWh is needed.

The register test is very time-consuming for meters without decimals. The best balance between short testing times and display reading functionality in the field is two decimal digits fix, or with a selectable high resolution by push button.

Thank you for reading. If you have remarks or questions, please contact us or use the comments-area below.

Leave a Reply

Your email address will not be published. Required fields are marked *